Page 177 - Catalog 26 2019
P. 177
APPENDIX A
WIRE AND CABLE DIMENSIONS
TFN/THHN/ Coaxial Cables
GAUGE XHHW RHH/RHW
MTW/THWN
18 AWG .09 ---- ---- TYPE DIA
16 AWG .10 ---- ----
14 AWG .10 .14 ----
12 AWG .12 .16 .18 RG-58/U .195
10 AWG .15 .18 .20 RG-59/U .242
8 AWG .22 .24 .27 RG-6/U .273
6 AWG .26 .28 .30 RG-6/UQ .298
4 AWG .33 .32 .35
3 AWG .36 .35 .38 Thermostat Cable
2 AWG .39 .38 .41
1 AWG .45 .44 .48
1/0 .49 .48 .52 TYPE DIA
2/0 .54 .52 .56
3/0 .59 .58 .61 18/2 .136
4/0 .65 .63 .67
250 MCM .72 .70 .73 18/3 .144
300 MCM .77 .75 .78 18/4 .158
350 MCM .82 .80 .83 18/5 .174
400 MCM .87 .85 .88 18/6 .184
500 MCM .95 .93 .96 18/7 .190
600 MCM 1.06 1.04 1.11 18/8 .208
700 MCM 1.13 .88 ---- 18/9 .224
750 MCM 1.16 1.14 1.22 18/10 .227
800 MCM 1.20 ---- ---- 18/12 .245
900 MCM 1.26 1.00 ----
1000 MCM 1.32 1.29 1.37
WIRE SIZE EQUIVALENCY CHART
When sizing compression lugs for flex, DLO and welding cables, the diameter varies from that of standard
building wire. The chart below will help you to find the equivalent wire size for proper lug fitment. Always check
manufacturer specifications for proper termination directions and follow all safety guidelines.
CLASS B&C FLEX WELDING CLASS B&C FLEX WELDING
BUILDING WIRE CABLE CABLE DLO BUILDING WIRE CABLE CABLE DLO
8 AWG 8 AWG ---- ---- 300 MCM 4/0 4/0 4/0
6 AWG 6 AWG ---- ---- 350 MCM ---- ---- 262 MCM
4 AWG ---- ---- ---- 400 MCM ---- ---- 313 MCM
3 AWG 4 AWG 4 AWG 4 AWG 500 MCM 350 MCM ---- 373 MCM
2 AWG ---- ---- ---- 600 MCM ---- ---- 444 MCM
1 AWG 2 AWG 2 AWG 2 AWG
650 MCM 500 MCM ---- 535 MCM
1/0 ---- 1 AWG 1 AWG
750 MCM ---- ---- 646 MCM
2/0 1/0 1/0 1/0
800 MCM ---- ---- ----
3/0 2/0 2/0 2/0
900 MCM ---- ---- ----
4/0 ---- 3/0 AWG 3/0 AWG
1000 MCM 750 MCM ---- 777 MCM
250 MCM ---- ---- ----
Posi-tech 800-548-6728 Fax: 800-457-5156 email: sales@posi-tech.com Page 177